WATER-COOLED CHILLERS Requirements:

• Manufacturer specification sheets for items installed must be submitted with the completed Rebate Application. Chiller specification sheets must include performance data, including full load efficiency, IPLV, and capacity in tons at AHRI standard rating conditions per AHRI Standard 550/590 test procedures. • “Path A” refers to chillers that are optimized for full load applications, while “Path B” refers to chillers that are optimized for part load applications. • Rebates are calculated based on performance data (including capacity) at AHRI standard rating conditions. • Provide capacity (tonnage) to the nearest whole number and all kW/ton values rounded appropriately to three decimal places (e.g., enter 0.6421 kW/ton as 0.642 kW/ton).

Equipment Type - Path

Capacity (tons)

Full Load (kW/ton)

Part Load (kW/ton)

Code

Rebate

Unit

<75

≤0.720 ≤0.690 ≤0.630 ≤0.580 ≤0.530 ≤0.580 ≤0.580 ≤0.530 ≤0.530 ≤0.530 ≤0.780 ≤0.750 ≤0.680 ≤0.625 ≤0.585 ≤0.695 ≤0.635 ≤0.595 ≤0.585 ≤0.585 ≤0.720 ≤0.690 ≤0.630 ≤0.580 ≤0.530 ≤0.580 ≤0.580 ≤0.530 ≤0.530 ≤0.530 ≤0.780 ≤0.750 ≤0.680 ≤0.625 ≤0.585 ≤0.695 ≤0.635 ≤0.595 ≤0.585 ≤0.585

≤0.600 ≤0.560 ≤0.540 ≤0.520 ≤0.500 ≤0.550 ≤0.550 ≤0.520 ≤0.500 ≤0.500 ≤0.470 ≤0.460 ≤0.410 ≤0.380 ≤0.350 ≤0.410 ≤0.370 ≤0.360 ≤0.350 ≤0.350 ≤0.600 ≤0.560 ≤0.540 ≤0.520 ≤0.500 ≤0.550 ≤0.550 ≤0.520 ≤0.500 ≤0.500 ≤0.470 ≤0.460 ≤0.410 ≤0.380 ≤0.350 ≤0.410 ≤0.370 ≤0.360 ≤0.350 ≤0.350

H4716* H4717* H4718* H4719* H4720* H4726* H4727* H4728* H4729* H4730* H4721* H4722* H4723* H4724* H4725* H4731* H4732* H4733* H4734* H4735*

Positive Displacement Water Cooled - A

≥75 to <150 ≥150 to <300 ≥300 to <600

$8/ton + $12.50/ton per 0.1 Delta Efficiency below max.

Ton

≥600 <150

≥150 to <300 ≥300 to <400 ≥400 to <600

Centrifugal Water Cooled - A

$8/ton + $12.50/ton per 0.1 Delta Efficiency below max.

Ton

≥600

<75

Positive Displacement Water Cooled - B

≥75 to <150 ≥150 to <300 ≥300 to <600

$8/ton + $12.50/ton per 0.1 Delta Efficiency below max.

Ton

≥600 <150

≥150 to <300 ≥300 to <400 ≥400 to <600

Centrifugal Water Cooled - B

$8/ton + $12.50/ton per 0.1 Delta Efficiency below max.

Ton

≥600

<75

N-H4716* N-H4717* N-H4718* N-H4719* N-H4720* N-H4726* N-H4727* N-H4728* N-H4729* N-H4730* N-H4721* N-H4722* N-H4723* N-H4724* N-H4725* N-H4731* N-H4732* N-H4733* N-H4734* N-H4735*

Positive Displacement Water Cooled - A

≥75 to <150 ≥150 to <300 ≥300 to <600

$4/ton + $9.00/ton per 0.1 Delta Efficiency below max.

Ton

≥600 <150

≥150 to <300 ≥300 to <400 ≥400 to <600

Centrifugal Water Cooled - A

$4/ton + $9.00/ton per 0.1 Delta Efficiency below max.

Ton

≥600

<75

Positive Displacement Water Cooled - B

≥75 to <150 ≥150 to <300 ≥300 to <600

$4/ton + $9.00/ton per 0.1 Delta Efficiency below max.

Ton

≥600 <150

≥150 to <300 ≥300 to <400 ≥400 to <600

Centrifugal Water Cooled - B

$4/ton + $9.00/ton per 0.1 Delta Efficiency below max.

Ton

≥600

*Complete Tables C1 and C2 on the Supplemental Data Sheet.