NEW CONSTRUCTION AND MAJOR RENOVATIONS Measure Description - Path A
Code
Incentive
Unit
$4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max.
Positive Displacement Water-Cooled, <75 tons, Full Load ≤0.720 kW/ton and Part Load ≤0.600 kW/ton
N-H4716*
Ton
Positive Displacement Water-Cooled, ≥75 tons and <150 tons, Full Load ≤0.690 kW/ton and Part Load ≤0.560 kW/ton
N-H4717*
Ton
Positive Displacement Water-Cooled, ≥150 tons and < 300 tons, Full Load ≤0.630 kW/ton and Part Load ≤0.540 kW/ton
N-H4718*
Ton
Positive Displacement Water-Cooled, ≥300 tons and <600 tons, Full Load ≤0.580 kW/ton and Part Load ≤0.520 kW/ton
N-H4719*
Ton
Positive Displacement Water-Cooled, ≥600 tons, Full Load ≤0.530 kW/ton and Part Load ≤0.500 kW/ton
N-H4720*
Ton
Centrifugal Water-Cooled, <150 tons, Full Load ≤0.580 kW/ton and Part Load ≤0.550 kW/ton
N-H4726*
Ton
Centrifugal Water-Cooled, ≥150 tons and <300 tons, Full Load ≤0.580 kW/ton and Part Load ≤0.550 kW/ton
N-H4727*
Ton
Centrifugal Water-Cooled, ≥300 tons and <400 tons, Full Load ≤0.530 kW/ton and Part Load ≤0.520 kW/ton
N-H4728*
Ton
Centrifugal Water-Cooled, ≥400 tons and <600 tons, Full Load ≤0.530 kW/ton and Part Load ≤0.500 kW/ton
N-H4729*
Ton
Centrifugal Water-Cooled, ≥600 tons, Full Load ≤0.530 kW/ton and Part Load ≤0.500 kW/ton
N-H4730*
Ton
Measure Description - Path B
Code
Incentive
Unit
$4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max. $4/ton + $90/ton per 1.0 Delta Efficiency below max.
Positive Displacement Water-Cooled, <75 tons, Full Load ≤0.780 kW/ton and Part Load ≤0.470 kW/ton
N-H4721*
Ton
Positive Displacement Water-Cooled, ≥75 tons and <150 tons, Full Load ≤0.750 kW/ton and Part Load ≤0.460 kW/ton
N-H4722*
Ton
Positive Displacement Water-Cooled, ≥150 tons and <300 tons, Full Load ≤0.680 kW/ton and Part Load ≤0.410 kW/ton
N-H4723*
Ton
Positive Displacement Water-Cooled, ≥300 tons and <600 tons, Full Load ≤0.625 kW/ton and Part Load ≤0.380 kW/ton
N-H4724*
Ton
Positive Displacement Water-Cooled, ≥600 tons, Full Load ≤0.585 kW/ton and Part Load ≤0.350 kW/ton
N-H4725*
Ton
Centrifugal Water-Cooled, <150 tons, Full Load ≤0.695 kW/ton and Part Load ≤0.410 kW/ton
N-H4731*
Ton
Centrifugal Water-Cooled, ≥150 tons and <300 tons, Full Load ≤0.635 kW/ton and Part Load ≤0.370 kW/ton
N-H4732*
Ton
Centrifugal Water-Cooled, ≥300 tons and <400 tons, Full Load ≤0.595 kW/ton and Part Load ≤0.360 kW/ton
N-H4733*
Ton
Centrifugal Water-Cooled, ≥400 tons and <600 tons, Full Load ≤0.585 kW/ton and Part Load ≤0.350 kW/ton
N-H4734*
Ton
Centrifugal Water-Cooled, ≥600 tons, Full Load ≤0.585 kW/ton and Part Load ≤0.350 kW/ton
N-H4735*
Ton
* Supplemental Data Sheet needed
PRO TIP Chillers are typically sized for the hottest day of the year but run at much less than full capacity the majority of the time. Selecting a chiller with excellent part-load performance and good loading and unloading characteristics will help maximize energy efficiency.