2024 Multifamily Catalog

BOILER CONTROLS AND BURNERS

General Requirements: Only natural gas equipment is eligible for incentives. Equipment added to boilers fueled by electric, propane, or oil is NOT eligible for incentives. Equipment added to redundant or backup boilers does not qualify.

OUTSIDE AIR RESET/CUTOUT CONTROLS Requirements: • Outside air temperature boiler reset and cutout control incentives are for retrofit projects only. New boilers equipped with these controls do not qualify. • System must have an outdoor temperature sensor installed in a shaded location on the north side of the building. • System must be set up so the minimum temperature is less than 10°F above boiler manufacturer’s recommended minimum return temperature (unless unusual circumstances require a higher setting). • For controls on multiple boilers to qualify, control strategy must stage the lag boiler(s) only after the first boiler stage(s) fail to maintain the water temperature called for by the reset control. • Provide input capacity of boilers (in MBh) controlled with outside air reset and cutout controls per the example below. • Must be a central plant type arrangement that serves multiple dwelling units in the multifamily building.

EQUIPMENT UPGRADES AND RETROFITS Measure Description

Code

Incentive

Unit

Outside Air Reset/Cutout Controls

H2221

$70.00

Control

EXAMPLE Outside Air Reset / Cutout Controls Use this example when applying for outside air resent/cutout controls that also requires boiler capacity in MEh. Reference the table when filling out section 7 on the Incentive Application.

Total Incentive (A x B)

Incentive Code Manufacturer Name

Model

Unit Measure # of Units (A)

Incentive per Unit (B)

H2221

ABC Controls

OA1234

Control

1

$70.00

$70.00

Boiler Capacity

MBh

500

BOILER COMBUSTION UPGRADES Requirements: • Boiler must be natural gas-fired, forced-draft boiler used for space heating that operates a minimum of 4,000 hours per year. • Installation on redundant or backup boilers does not qualify for an incentive. • Boiler input capacity must be entered in boiler horsepower (BHP). To convert, use 1 BHP = 33.476 MBh. High turndown burner must be able to provide efficient combustion at a 10:1 turndown ratio or greater. The turndown ratio must be clearly shown on a manufacturer’s spec sheet or similar documentation. • High turndown burner incentives (H2203 and H5237) are eligible on boilers ≤ 1,000 BHP. Boilers > 1,000 BHP may be eligible for custom incentives. • Invoices must be attached and include the manufacturer name and model number of linkageless controls, O 2 trim, and high turndown burner equipment. • Must be a central plant type arrangement that serves multiple dwelling units in the multifamily building.

EQUIPMENT UPGRADES AND RETROFITS Measure Description

Code

Incentive

Unit

Linkageless Controls

H2205

$18.00

BHP

O 2 Trim Controls

H2206

$5.00

BHP

High Turndown Burner, Retrofit on Existing Boiler

H2203

$12.00

BHP

High Turndown Burner, New Boiler Replacement

H5237

$12.00

BHP

Incentive amount is limited to 50% of the project cost, including equipment and external labor.

18